1. INFORMACIÓN GENERAL............................................................3 2. SITUACIÓN ACTUAL....................................................................4 2.1 ARQUITECTURA.......................................................................................................4 2.2 INSTALACIÓN ELÉCTRICA........................................................................................5 2.3 ILUMINACION.........................................................................................................12 2.4 CLIMATIZACIÓN Y ACS...........................................................................................30
3. PROPUESTAS DE MEJORA.........................................................34 3.1 TARIFA DE CONTRATACIÓN ELÉCTRICA.................................................................35 3.2 BATERÍA DE CONDENSADORES.............................................................................36 3.3 SUSTITUCIÓN DE FLUORESCENTES T8 POR ECOTUBO T5.....................................38 3.4 SUSTITUCIÓN DE LUMINARIAS INCANDESCENTES POR LED..................................43 3.5 INSTALACIÓN DE DETECTORES DE PRESENCIA.....................................................48 3.6 INSTALACIÓN DE INTERRUPTORES CREPUSCULARES............................................50 3.7 EQUIPO MONITORIZACIÓN EFERGY.......................................................................52 3.8 INSTALACIÓN DE RELOJ PROGRAMABLE................................................................54 3.9 RESUMEN PROPUESTAS DE MEJORA......................................................................55
2
1. INFORMACIÓN GENERAL El establecimiento objeto del estudio es el edificio situado en la calle Ibaiondo 6 de Orozko. Se trata de un edificio que alberga el colegio del pueblo. Los datos generales son los siguientes:
Nombre del local Uso principal Dirección Municipio Provincia
Colegio público de Orozko Colegio C/ Ibaiondo 6, bajo 1 Orozko Bizkaia
* Todos los datos de costes, ahorros e inversiones de este informe no tienen incluido el I.V.A.
3
2. SITUACIÓN ACTUAL 2.1 ARQUITECTURA
Las ventanas son de cristal doble con cámara y marcos de PVC. El estado de los cerramientos se considera correcto.
4
2.2 INSTALACIÓN ELÉCTRICA 2.2.1 CUADRO ELÉCTRICO GENERAL
Se ha revisado el cuadro eléctrico y en líneas generales la instalación se considera correcta. Dispone de elementos de protección generales frente a cortocircuitos y sobrecargas, así como frente a derivaciones mediante interruptor automático y diferenciales debidamente dimensionados (ver anexo I). Se observa una correcta sectorización de diferentes circuitos de consumo debidamente señalizados por lo que se facilita la detección de las líneas en las que pueden surgir anomalías y así simplificar las actuaciones correctivas pertinentes.
2.2.2 INSTALACIÓN ELÉCTRICA GENERAL Se respetan las secciones mínimas requeridas por reglamento y el estado del aislamiento del cableado es correcto.
2.2.3 INVENTARIO GENERAL DE EQUIPOS DE CONSUMO A continuación se presenta el inventario de los equipos consumidores de energía eléctrica más representativos del edificio agrupado en los siguientes servicios: iluminación,
5
climatización, fuerza y otros. En él se define la potencia instalada en cada servicio, el consumo eléctrico estimado y su coste económico y medioambiental. (Inventario completo en el anexo II). * Los consumos y costes del inventario de equipos son orientativos y con finalidad informativa. No incluyen el impuesto eléctrico y no se tiene en cuenta el coste del término fijo de potencia. Los consumos y costes anuales reales se indican en el siguiente apartado, facturación de energía eléctrica.
POTENCIA TOTAL INSTALADA (kW)
CONSUMO ELÉCTRICO ANUAL (kWh)
EMISIONES G.E.I. ANUALES (TmCO2)
COSTE ELÉCTRICO ANUAL (€)
ILUMINACIÓN
52,89
42.202,49
5825,14
19,3709
CLIMATIZACIÓN
57,35
9.524,25
1263,66
4,3716
FUERZA
57,73
7.490,62
1101,44
4,4627
OTROS
55,6474
22.729,34
2710,95
9,4083
TOTAL
223,62
81.946,70
10.901,19
37,6135
El reparto de potencia de equipos instalados en el edificio es el siguiente: R EP A R T O DE P O T ENC IA (%) C O LEG IO OTROS 25%
FUERZA 26%
ILUMINACIÓN 24%
CLIMATIZACIÓN 25%
El reparto del consumo eléctrico en el edificio es el siguiente:
6
R EP A R T O DE C O NSUMO ELÉC T R IC O (%) C O LEG IO OTROS 28%
ILUMINACIÓN 51%
FUERZA 9% CLIMATIZACIÓN 12%
Podemos observar que el consumo eléctrico varía respecto a la potencia instalada. Se observa que los equipos de encendido prolongado, como son la iluminación y los equipos denominados como otros (ofimática, telefonía, videovigilancia...), a pesar de no destacar en cuanto a potencias eléctricas de instalación frente a otros equipos de fuerza, son los que mayor consumo eléctrico tienen a lo largo del año, por que funcionan durante muchas horas al día. La iluminación es la instalación que más energía eléctrica consume llegando al 51% del total, seguido de otros equipos (28%).
7
2.2.4 FACTURACIÓN DE ENERGÍA ELÉCTRICA El contrato vigente es el siguiente: Comercializadora:
GAS NATURAL FENOSA
Tipo de Tarifa Contratada:
3.0A
Potencia contratada:
45 kW
Consumo de energía diaria:
- kWh
Consumo de energía anual:
80.786 kWh
Término de energía P1:
0,173972
€/kWh
Término de energía P2:
0,132678
€/kWh
Término de energía P3:
0,074668
€/kWh
Término de potencia:
2,625556
€/kW y mes
El horario de cada periodo tarifario es el siguiente: Invierno:
Verano:
P1 o Punta:
de 18h a 22h
P2 o Llano:
de 8h a 18h y de 22h a 24h
P3 o Valle:
de 11h a 15h de 8h a 11h y de 15h a 24h
de 0h a 8h
de 0h a 8h
El consumo de energía eléctrica del edificio objeto del estudio estimado en el periodo entre noviembre de 2011 y octubre de 2012 es el que se muestra a continuación (según facturas facilitadas): TÉRMINO DE ENERGÍA P1
P2
P3
TOTAL
nov-11
1.402
5.051
1.091
7.544
dic-11
1100
6550
1200
8.850
ene-12
876
4271
1046
6.193
feb-12
1.460
7.240
1.498
10.198
mar-12
1.465
7.247
1.498
10.210
abr-12
1.922
4.434
1.261
7.617
may-12
2.479
4.062
1.156
7.697
jun-12
2.006
3.157
1.017
6.180
jul-12
858
1.394
763
3.015
ago-12
415
1.103
788
2.306
sep-12
1.320
2.090
835
4.245
oct-12 TOTAL
1.391
4.236
1.104
6.731
16.694
50.835
13.257
80.786
8
C O NSUMO E LÉC T R IC O ME NSUA L P O R P E R IO DO S (kWh ) C O LEG IO 8.000 7.000
P1
6.000 5.000
P2
4.000 3.000
P3
2.000 1.000 0 nov-11
dic-11
ene-12 feb-12 mar-12 abr-12 may-12 jun-12
jul-12
ago-12 sep-12
oct-12
El consumo en punta entre abril y junio (periodo estival) es mayor que entre noviembre y marzo (periodo invernal). Esto se debe a que el periodo de facturación punta en verano es de 11:00 a 15:00 (en las que el colegio se encuentra abierto) y en invierno en cambio, es de 18:00 a 22:00 horas (en las que el colegio se encuentra cerrado). El consumo total anual de energía eléctrica en el establecimiento objeto del estudio es de 80.786 kWh, siendo el consumo medio mensual de 6.732 kWh. Los importes totales de los términos de energía y potencia del establecimiento objeto del estudio son:
IMPORTE TERMINO DE POTENCIA
IMPORTE TÉRMINO DE ENERGÍA
IMPORTE TOTAL
1.466,21 €
11.182,78 €
12.648,99
En las facturas facilitadas se observa que la potencia contratada (45kW) se ajusta correctamente a la demanda de potencia simultánea, aunque se sobre pase en algunos casos y se paguen esos excesos. La facturación de potencia en la tarificación 3.0A es del 85% (38,25kW) si la demanda no llega al 85% de la contratada, como pueden ser los meses de julio y agosto, o el periodo P3. La facturación de la potencia en la tarificación 3.0A es el de la lectura del maxímetro entre el 85% y el 105% de la potencia contratada.
9
A partir del 105%, la potencia a facturar es igual al valor registrado en el maxímetro más el doble de la diferencia entre la lectura del maxímetro y el 105% de la contratada. En las siguientes gráficas se pueden observar las demandas de potencia, la potencia contratada y la facturada:
Potencia periodo P1 o Punta 80 60 40 20 0 1
2
P1
3
4
5
6
7
8
Potencia contratada
9
10
11
12
Potencia facturada
Potencia periodo P2 o Llano 80 60 40 20 0 1
2
P2
3
4
5
6
7
8
Potencia contratada
9
10
11
12
Potencia facturada
Potencia periodo P3 o Valle 50 40 30 20 10 0 1 P3
2
3
4
5
6
7
Potencia contratada
8
9
10
11
12
Potencia facturada
2.2.4.2 PENALIZACIONES POR CONSUMO DE ENERGÍA REACTIVA
El Reglamento penaliza los consumos superiores al 33% de energía reactiva respecto a la del consumo de energía activa en los periodos 1 o Punta y 2 o Llano.
10
Esta penalización también suele expresarse como un factor de potencia mínimo exigido y fijado en 0,95 (cos(phi)), límite mínimo marcado por normativa. El establecimiento tiene una penalización media por consumo de reactiva anual en las facturas facilitadas de 192,55€. Se trata de una penalización por no cumplir los requisitos mínimos de consumo con un factor de potencia de 0,95, y además hay que tener en cuenta que las penalizaciones van en aumento o incluso el factor de potencia del consumo va decreciendo (y aumentando la penalización) únicamente por la antigüedad de los equipos.
11
2.3 ILUMINACION A continuación, se muestra el inventario de equipos de iluminación que se utilizan diferenciando las diversas zonas:
12
EDIFICIO EDUCACIÓN PRIMARIA:
13
14
15
16
17
18
EDIFICIO EDUCACIÓN INFANTIL:
19
20
21
BARRACÓN 1:
22
BARRACÓN 2:
23
24
EXTERIOR:
25
La distribución de las potencias de las luminarias instaladas es la siguiente: P O T ENC IA INST A LA DA P O R T IP O S DE LUMINA R IA S (Kw) C O LEG IO 45 40,51 40
FLUORESCENTE T8 FLUORESCENTE T12
35
POTENCIA (kW)
LEDTUBE 30
BAJO CONSUMO INCANDESCENTE
25
HALOGENURO METÁLICO HALÓGENA
20
VSAP 15 8,80
10 5
1,04
0,70
0,03
1,28
0,40
0,60
0
Se observa que los tipos de luminaria más empleados en cuanto a potencia instalada en el edificio objeto del estudio son los fluorescentes T8. En cuanto a cantidad, la luminaria más empleada es el fluorescente T8 de 36W:
TIPO DE LUMIRARIA
CANTIDAD
FLUORESCENTE T8 58W
177
FLUORESCENTE T8 36W
593
FLUORESCENTE T8 18W
6
FLUORESCENTE T12 65W
6
FLUORESCENTE T12 40W
12
LEDTUBE 24W
52
LEDTUBE 19W
8
BAJO CONSUMO 11W
2
INCANDESCENTE 100W INCANDESCENTE 40W
10 7
HALOGENURO METÁLICO 150W
20
HALOGENURO METÁLICO 400W
12
HALÓGENA 50W
8
VSAP 70W
4
VSAP 250W TOTAL
1 918
Con los datos anteriormente obtenidos, podemos destacar que el 82% de las luminarias empleadas son no eficientes.
26
2.3.1 NIVELES DE ILUMINACION La Norma Europea UNE-EN 12464-1, respecto a la iluminación de los lugares de trabajo en interior, define los parámetros recomendados para los distintos tipos de áreas, tareas y actividades. Las recomendaciones de esta norma, en términos de cantidad y calidad del alumbrado, contribuyen a diseñar sistemas de iluminación que cumplen las condiciones de calidad y confort visual, y permite crear ambientes agradables para los usuarios de las instalaciones.
Según la medición realizada durante la auditoria con un luxómetro digital KL 1330, los
PRIMARIA
niveles de iluminación en el local son los que mostramos a continuación:
UBICACIÓN
ILUMINACIÓN (lux)
NORMA
OBSERVACIONES
PISO 0 ENTRADA
515
200
POR ENCIMA DEL NIVEL RECOMENDADO
SALA PORTERO
628
300
POR ENCIMA DEL NIVEL RECOMENDADO
BAÑO PROFESORES
620
200
POR ENCIMA DEL NIVEL RECOMENDADO
HIPI
960
200
POR ENCIMA DEL NIVEL RECOMENDADO
27
IGE-AMPA
920
200
POR ENCIMA DEL NIVEL RECOMENDADO
MESA DIRECTOR
930
300
POR ENCIMA DEL NIVEL RECOMENDADO
DIRECCIÓN
510
500
CORRECTO
HALL SALA PROFESORES
536
200
POR ENCIMA DEL NIVEL RECOMENDADO
SALA PROFESORES
925
300
POR ENCIMA DEL NIVEL RECOMENDADO
SALA LIMPIEZA
42
100
POR DEBAJO DEL NIVEL RECOMENDADO
COMEDOR
495
200
POR ENCIMA DEL NIVEL RECOMENDADO
COCINA
353
500
POR DEBAJO DEL NIVEL RECOMENDADO
DESPENSA
452
100
POR ENCIMA DEL NIVEL RECOMENDADO
BAÑO HOMBRES
786
200
POR ENCIMA DEL NIVEL RECOMENDADO
BAÑO MUJERES
648
200
POR ENCIMA DEL NIVEL RECOMENDADO
CLASE 3B
780
300
POR ENCIMA DEL NIVEL RECOMENDADO
PASILLO 1º CICLO
474
100
POR ENCIMA DEL NIVEL RECOMENDADO
3A
905
300
POR ENCIMA DEL NIVEL RECOMENDADO
4B
905
300
POR ENCIMA DEL NIVEL RECOMENDADO
3º CURSO
900
300
POR ENCIMA DEL NIVEL RECOMENDADO
GIMNASIO
427
300
POR ENCIMA DEL NIVEL RECOMENDADO
VESTUARIO CHICAS
240
200
CORRECTO
VESTUARIO CHICOS
195
200
CORRECTO
BAÑO MUJERES
693
200
POR ENCIMA DEL NIVEL RECOMENDADO
CURSO 6B
880
300
POR ENCIMA DEL NIVEL RECOMENDADO
4º CURSO MÚSICA
336
300
CORRECTO
BAÑOS
570
200
POR ENCIMA DEL NIVEL RECOMENDADO
SALA ORDENADOR
600
300
POR ENCIMA DEL NIVEL RECOMENDADO
28
INFANTIL BARRACONES
SALA TUTORÍAS
676
300
POR ENCIMA DEL NIVEL RECOMENDADO
SALA PROFESORES
824
300
POR ENCIMA DEL NIVEL RECOMENDADO
BAÑO PISO 0
321
200
POR ENCIMA DEL NIVEL RECOMENDADO
ENFERMERÍA
388
300
CORRECTO
BAÑO MUJERES
272
200
CORRECTO
BAÑO HOMBRES
157
200
CORRECTO
PASILLO PISO 0
657
100
POR ENCIMA DEL NIVEL RECOMENDADO
PASILLO PISO 1
475
100
POR ENCIMA DEL NIVEL RECOMENDADO
SALA MÚSICA
161
300
POR DEBAJO DEL NIVEL RECOMENDADO
ENTRADA BARRACÓN
250
200
CORRECTO
SALA DEBERES
310
200
POR ENCIMA DEL NIVEL RECOMENDADO
BAÑOS BARRACÓN 1
100
200
POR DEBAJO DEL NIVEL RECOMENDADO
BAÑOS BARRACÓN 2
850
200
POR ENCIMA DEL NIVEL RECOMENDADO
SALA INGLÉS
224
300
POR DEBAJO DEL NIVEL RECOMENDADO
PLANTA 1 ZONA COMÚN
250
100
POR ENCIMA DEL NIVEL RECOMENDADO
BAÑOS
180
200
CORRECTO
BAÑOS
250
200
CORRECTO
BIBLIOTECA
150
500
POR DEBAJO DEL NIVEL RECOMENDADO
ALMACÉN
430
100
POR ENCIMA DEL NIVEL RECOMENDADO
29
2.4 CLIMATIZACIÓN Y ACS 2.4.1 EQUIPOS El colegio dispone de 5 termos eléctricos de distinto volumen y potencias y un calentador que se alimenta de gas propano para la obtención de ACS. El calentador es de la marca VAILLANT modelo Turbomag-17 y las siguientes características:
Datos Técnicos: Cámara de combustión: Estanca Caudal de agua (AT =25K): 17 l/min Modulación: Automática Selección salto térmico (AT): Ajustable K Funcionamiento: Consumo calorífico nominal: 32,9kW Potencia nominal: 29kW Modulación de potencia: 8,6-29kW Rendimiento nominal: 89%
Además de los equipos ya mencionados, existe un sistema de District Heating del que se obtiene calor para calefacción. El calor (la energía térmica) se distribuye por una red urbana, del mismo modo en que se hace con el gas o el agua. Para ello se dispone de 2 válvulas y 4 bombas.
30
2.4.2 CONSUMO PELLET El consumo de energía térmica del edificio objeto del estudio estimado en el periodo entre enero de 2012 y diciembre de 2012 es el que se muestra a continuación (según datos facilitados): CONSUMO (kWh) ene-12
1.981
feb-12
12.800
mar-12
7.390
abr-12
3.320
may-12
2.550
jun-12
1.100
jul-12
0
ago-12
0
sep-12
0
oct-12
0
nov-12
7.190
dic-12
6.651
TOTAL
42.982
C O NSUMO DE ENER G ÍA T ÉR MIC A MENSUA L (kW h) C O LEG IO 14.000 12.000 10.000 8.000 6.000 4.000 2.000 0 ene-12 feb-12 mar-12 abr-12 may-12 jun-12
jul-12
ago-12 sep-12
oct-12 nov-12 dic-12
El consumo total anual de energía térmica en el establecimiento objeto del estudio es de 42.982 kWh, siendo el consumo medio mensual de 3.582 kWh. Los importes totales de los términos fijo y variable del establecimiento objeto del estudio son:
IMPORTE TERMINO FIJO
IMPORTE TÉRMINO VARIABLE
IMPORTE TOTAL
13.059,70 €
1.717,60 €
14.777,30 €
31
Se puede observar que el coste tanto anual del término fijo es mucho mayor que el coste del término variable, algo poco habitual. En las siguientes graficas se representa la diferencia de ambos términos.
C O ST E A NUA L ENER G ÍA T ÉR MIC A (€) C O LEG IO
C O ST E A NUA L ENER G IA T ÉR MIC A (%) C O LEG IO
16.000 € TERMINO VARIABLE 12%
14.000 € 12.000 €
TERMINO FIJO 88%
10.000 € 8.000 €
TERMINO VARIABLE TERMINO FIJO
6.000 € 4.000 € 2.000 € 0€
C O ST E MENSUA L DE ENER G ÍA T ÉR MIC A (€) C O LEG IO 2.500 € 2.000 € 1.500 €
TERMINO VARIABLE TERMINO FIJO
1.000 € 500 € 0€ ene-12 feb-12 mar-12 abr-12 may-12 jun-12
jul-12
ago-12 sep-12 oct-12 nov-12 dic-12
32
2.4.3 COMPARATIVA COMBUSTIBLES En este apartado se analizará el coste que supondría la generación de la energía térmica con otros combustibles.
C O MP A R A T IV A C O ST E A NUA L DIST INT O S C O MB UST IB LE S (€) C O LEG IO 25.000 € 20.000 €
19.598,29 €
15.000 € 10.000 € 5.197,33 €
4.601,82 €
3.992,10 €
GASOIL
PELLET
GAS NATURAL
5.000 € 0€ ACTUAL
Como puede observarse, el gasto se reduce considerablemente si se obtiene la energía térmica necesaria mediante gas natural.
33
3. PROPUESTAS DE MEJORA En este apartado se expondrán las propuestas de mejora detectadas para las instalaciones energéticas del establecimiento objeto del estudio. Se desarrollará la idea, se valorará económicamente la actuación y se presentará el ahorro energético en kWh de energía, el ahorro económico en euros y la reducción de emisiones de gases contaminantes a la atmósfera.
34
3.1 TARIFA DE CONTRATACIÓN ELÉCTRICA Del análisis de las condiciones de la contratación eléctrica actual respecto de las ofertas disponibles en el mercado a fecha de 10 de enero de 2013 los resultados son los siguientes: ENDESA
IMPORTE ANUAL
AHORRO %
€
EON
ACTUAL
12.648,99 €
-
-
ER +3
11.570,29 €
8,53%
1.078,70 €
FACTOR ENERGIA
12.352,55 €
2,34%
296,44 €
VILLAR MIR EON
12.753,93 €
-0,83%
-104,94 €
12.949,30 €
-2,37%
-300,32 €
ENDESA
13.020,44 €
-2,94%
-371,45 €
VILLAR MIR FACTOR ENERGIA ER +3 -500 €
0€
500 €
1.000 €
1.500 €
El balance es el siguiente:
ENERGÍA (kWh)
COSTE (€)
Tm CO2
SISTEMA ACTUAL
80.786,00
12.648,99 €
37,08
SISTEMA PROPUESTO
80.786,00
11.570,29 €
37,08
-
1.078,70 €
-
AHORRO /AÑO
Y el cuadro de amortización:
MEJORA 1 INVERSIÓN (€)
-
AHORRO ENERGÉTICO (%)
-
AHORRO ENERGÉTICO (kWh)
-
AHORRO ECONÓMICO (%)
8,53%
AHORRO ECONÓMICO ANUAL TOTAL (€)
1.078,70 €
AMORTIZACIÓN SIMPLE* (AÑOS)
INMEDIATA
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
35
3.2 BATERÍA DE CONDENSADORES
Existe penalización por exceso de consumo de energía reactiva en el local objeto del estudio. A continuación se presenta el consumo de energía reactiva: CONSUMO DE CONSUMO DE ENERGÍA REACTIVA ENERGÍA REACTIVA ENERGIA REACTIVA COS φ DEL TOTAL CONSUMIDA CONSUMO RESPECTO DE LA PENALIZADA (kVArh) ACTIVA (%) (kVArh) P1
P2
PENALIZACIÓN DE EXCESO DE CONSUMO DE ENERGÍA REACTIVA (€)
P1
P2
P1
P2
P1
P2
P1
P2
558
2230
39,80%
44,15%
95,34
563,17
0,93 0,91
3,96
23,40
343
2616
31,18%
39,94%
0,00
454,50
0,95 0,93
0,00
18,89
250
1488
28,54%
34,84%
0,00
78,57
0,96 0,94
0,00
3,26
420
2700
28,77%
37,29%
0,00
310,80
0,96 0,94
0,00
12,91
440
2724
30,03%
37,59%
0,00
332,49
0,96 0,94
0,00
13,82
677
1565
35,22%
35,30%
42,74
101,78
0,94 0,94
1,78
4,23
1024
1602
41,31%
39,44%
205,93
261,54
0,92 0,93
8,56
10,87
1024
1405
51,05%
44,50%
362,02
363,19
0,89 0,91
15,04
15,09
479
601
55,83%
43,11%
195,86
140,98
0,87 0,92
8,14
5,86
240
516
57,83%
46,78%
103,05
152,01
0,87 0,91
4,28
6,32
732
891
55,45%
42,63%
296,40
201,30
0,87 0,92
12,32
8,36
562
1667
40,40%
39,35%
102,97
269,12
0,93 0,93
4,28
11,18
58,35
134,20 192,55 €
La penalización anual por exceso de consumo de energía reactiva es de 192,55€. A continuación se calcula la batería de condensadores necesaria para evitar la penalización:
CONSUMO ENERGÍA ACTIVA (kWh) MES 1 MES 2 MES 3 MES 4 MES 5
CONSUMO ENERGÍA REACTIVA (kVArh)
ENERGÍA APARENTE (kVA)
ENERGÍA APARENTE (kVA)
COS φ
TAG φ
MAXIMETRO
POTENCIA DE BATERÍA (kVAr)
P1
1.402
558
2276968
1.508,96
0,9291
0,3980
49
19,50
P2
5.051
2.230
30485501
5.521,37
0,9148
0,4415
47
20,75
P1
1.100
343
1327649
1.152,24
0,9547
0,3118
23
7,17
P2
6.550
2.616
49745956
7.053,08
0,9287
0,3994
50
19,97
P1
876
250
829876
910,98
0,9616
0,2854
26
7,42
P2
4.271
1.488
20455585
4.522,79
0,9443
0,3484
51
17,77
P1
1.460
420
2308000
1.519,21
0,9610
0,2877
26
7,48
P2
7.240
2.700
59707600
7.727,07
0,9370
0,3729
50
18,65
P1
1.465
440
2339825
1.529,65
0,9577
0,3003
28
8,41
36
MES 6 MES 7 MES 8 MES 9 MES 10 MES 11 MES 12 ANUAL
P2
7.247
P1
1.922
P2
4.434
P1
2.479
P2
4.062
P1
2.006
P2
3.157
P1
858
479
P2
1.394
601
P1
415
240
P2
1.103
516
P1
1.320
732
P2
2.090
891
P1
1.391
P2
4.236
P1
16.694
P2
50.835
2.724
59939185
7.742,04
0,9361
0,3759
55
20,67
677
4152413
2.037,75
0,9432
0,3522
41
14,44
1.565
22109581
4.702,08
0,9430
0,3530
53
18,71
1.024
7194017
2.682,17
0,9243
0,4131
51
21,07
1.602
19066248
4.366,49
0,9303
0,3944
50
19,72
1.024
5072612
2.252,25
0,8907
0,5105
44
22,46
1.405
11940674
3.455,53
0,9136
0,4450
47
20,92
965605
982,65
0,8731
0,5583
40
22,33
2304437
1.518,04
0,9183
0,4311
36
15,52
229825
479,40
0,8657
0,5783
6
3,47
1482865
1.217,73
0,9058
0,4678
7
3,27
2278224
1.509,38
0,8745
0,5545
11
6,10
5161981
2.272,00
0,9199
0,4263
10
4,26
562
2250725
1.500,24
0,9272
0,4040
44
17,78
1.667
20722585
4.552,21
0,9305
0,3935
47
18,50
6.749
324238637
18.006,63
0,9271
0,4043
51
20,62
20.005
2984397250
54.629,64
0,9305
0,3935
55
21,64
Se opta por una batería de condensadores de 43,75kVAr (440V) de capacidad con una composición de 6,25+12,5+12,5. El balance de la mejora es el siguiente:
ENERGÍA (kWh)
COSTE (€)
Tm CO2 -
SISTEMA ACTUAL
-
192,55 €
SISTEMA PROPUESTO
-
0,00 €
-
AHORRO /AÑO
-
192,55 €
-
Y el cuadro de amortización es el siguiente:
MEJORA 2 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh)
1.986,06 € -
AHORRO ECONÓMICO (%)
100,00%
AHORRO ECONÓMICO ANUAL TOTAL (€)
192,55 €
AMORTIZACIÓN SIMPLE* (AÑOS)
10,3
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
37
3.3 SUSTITUCIÓN DE FLUORESCENTES CONVENCIONALES T8 POR ECOTUBO T5 Esta medida de ahorro consiste en el cambio de los fluorescentes “habituales” T8 de 26mm de grosor por los modelos Ecotubo T5 de 16mm de grosor de menor consumo y mayor durabilidad. Los Ecotubo tienen incorporados el balastro electrónico reduciendo así el coste de instalación (solo hay que sustituir el tubo convencional por el Ecotubo y retirar el cebador).
Características:
Vida cuatro veces superior a un tubo convencional (50.000h balastro y 22.000h tubo).
Ahorro energético garantizado de un 50%.
No parpadea ni produce ruidos.
Admite distorsión de la señal eléctrica hasta un 15%.
Regulable en intensidad.
Factor de potencia mayor de 0,95.
Reproducción cromática superior al 85%.
Bajo coeficiente de distorsión con aplicación nanotecnológica.
Reduce las emisiones de CO2.
Se adapta del T8 al T12 y a rápidas instalaciones sin cablear.
38
3.3.1 SUSTITUCIÓN DE FLUORESCENTES T8 58W POR ECOTUBO T5 35W: 5 HORAS DE FUNCINAMIENTO Esta propuesta de mejora es para la sustitución de los 145 fluorescentes convencionales T8 por fluorescentes T5 a los que se les han estimado 5 horas de funcionamiento al día en el inventario. Este cambio se considera de interés debido a que supone un ahorro energético en torno al 40% del consumo, siendo muy económica en cuanto a la inversión. El cambio se justifica porque la luminosidad proporcionada por los fluorescentes de menor potencia es del mismo orden (incluso mayor) que la luminosidad dada por los fluorescentes convencionales y la vida útil cuadruplica a la de las convencionales. A partir de los datos anteriores, se estima el ahorro en consumo de energía eléctrica y en mantenimiento que se puede alcanzar mediante la instalación de estos fluorescentes de mayor eficacia:
AHORRO EN CONSUMO DE ENERGÍA ELÉCTRICA POTENCIA LÁMPARA (W)
CONSUMO TOTAL POR LUMINARIA (W)
CONSUMO ANUAL TOTAL (kWh)
COSTE TOTAL ANUAL (€)
FLUORESCENTE (T8)
58
68,43
10.913,79
1.550,48 €
ECOTUBO (T5)
35
40,76
6.500,95
923,56 €
AHORRO (€)
626,91 €
AHORRO EN MANTENIMIENTO DE INSTALACIÓN
Nº CAMBIOS /AÑO
COSTE SUSTITUCIÓN LÁMPARAS AÑO (€)
Nº CAMBIOS CEBADOR/AÑO
COSTE SUSTITUCIÓN CEBADOR (€)
MANO DE OBRA SUSTITUCIONES (€)
FLUORESCENTE (T8)
0,15
55,08 €
0,044
4,79 €
69,12 €
128,98 €
ECOTUBO (T5)
0,03
18,46 €
-
-
12,08 €
30,55 €
TOTAL
AHORRO (€) 98,44 €
En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de las propuestas de mejora, incluyendo gasto de energía, coste y toneladas de CO2:
ENERGÍA (kWh)
COSTE (€)
Tm CO2
10.913,79
1.679,46 €
5,0094
SISTEMA PROPUESTO
6.500,95
954,11 €
2,9839
AHORRO /AÑO
4.412,84
725,35 €
2,03
SISTEMA ACTUAL
39
Y el cuadro de amortización es el siguiente:
MEJORA 3 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
6.297,83 € 40,43% 4.412,84 43,19% 725,35 € 8,7
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
40
3.3.2 SUSTITUCIÓN DE FLUORESCENTES T8 36W POR ECOTUBO T5 28W: 5 HORAS DE FUNCIONAMIENTO Esta propuesta de mejora es para la sustitución de los 416 fluorescentes convencionales T8 por fluorescentes T5 a los que se les han estimado 5 horas de funcionamiento al día en el inventario. Este cambio se considera de interés debido a que supone un ahorro energético en torno al 30% del consumo, siendo muy económica en cuanto a la inversión. El cambio se justifica porque la luminosidad proporcionada por los fluorescentes de menor potencia es del mismo orden (incluso mayor) que la luminosidad dada por los fluorescentes convencionales y la vida útil cuadruplica a la de las convencionales. A partir de los datos anteriores, se estima el ahorro en consumo de energía eléctrica y en mantenimiento que se puede alcanzar mediante la instalación de estos fluorescentes de mayor eficacia:
AHORRO EN CONSUMO DE ENERGÍA ELÉCTRICA POTENCIA LÁMPARA (W)
CONSUMO TOTAL POR LUMINARIA (W)
CONSUMO ANUAL TOTAL (kWh)
COSTE TOTAL ANUAL (€)
FLUORESCENTE (T8)
36
46,83
21.427,12
3.044,07 €
ECOTUBO (T5)
28
32,23
14.749,45
2.095,40 €
AHORRO (€)
948,67 €
AHORRO EN MANTENIMIENTO DE INSTALACIÓN
Nº CAMBIOS /AÑO
COSTE SUSTITUCIÓN LÁMPARAS AÑO (€)
Nº CAMBIOS CEBADOR/AÑO
COSTE SUSTITUCIÓN CEBADOR (€)
MANO DE OBRA SUSTITUCIONES (€)
FLUORESCENTE (T8)
0,15
143,99 €
0,044
13,73 €
198,29 €
356,01 €
ECOTUBO (T5)
0,03
52,97 €
-
-
34,67 €
87,64 €
TOTAL
AHORRO (€) 268,38 €
En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de las propuestas de mejora, incluyendo gasto de energía, coste y toneladas de CO2:
ENERGÍA (kWh)
COSTE (€)
Tm CO2
SISTEMA ACTUAL
21.427,12
3.400,08 €
9,8350
SISTEMA PROPUESTO
14.749,45
2.183,04 €
6,7700
6.677,67
1.217,05 €
3,07
AHORRO /AÑO
41
Y el cuadro de amortización es el siguiente:
MEJORA 4 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
16.513,47 € 31,16% 6.677,67 35,79% 1.217,05 € 13,6
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
42
3.4 SUSTITUCIÓN DE LUMINARIAS INCANDESCENTES POR LUMINARIAS CON TECNOLOGÍA LED Esta medida de ahorro consiste en el cambio de lámparas incandescentes por luminarias con tecnología led de menor consumo y mayor durabilidad. Las lámparas led son de sustitución directa, ya que tienen el mismo casquillo (E27) que las luminarias incandescentes.
Características: • Vida diez veces superior a las incandescentes (más de 25.000h). • Ahorro energético de más de un 70%. • El Led tiene un rendimiento Lm/W elevado respecto a otras fuentes de luz. • La baja emisión de calor y la menor dispersión de luz en direcciones no deseadas, hacen que sea una de las fuentes de luz más eficientes del mercado. • Su emisión de calor es mínima y se proyecta en dirección contraria a la emisión de la luz. • El Led permite un control absoluto de la luz: intensidad, temperatura, colores. • Productos testados y certificados en los laboratorios AT4 Wireless adscritos a ENAC. • Reduce las emisiones de CO2.
43
3.4.1 SUSTITUCIÓN DE LUMINARIAS INCANDESCENTE DE 40W POR LUMINARIAS LED DE 8W: ENTRADA/VESTÍBULO Esta propuesta de mejora es para la sustitución de las 6 luminarias incandescentes de la entrada/vestíbulo del colegio. Este cambio se considera de interés debido a que supone un ahorro energético en torno al 70% del consumo, siendo muy económica en cuanto a la inversión. El cambio se justifica porque la luminosidad proporcionada por los led es del mismo orden (incluso mayor) que la luminosidad dada por las incandescentes. A partir de los datos anteriores, se estima el ahorro en consumo de energía eléctrica y en mantenimiento que se puede alcanzar mediante la instalación de estas luminarias de mayor eficacia: Ahorro en consumo de energía eléctrica: UDS.
POTENCIA (W)
POTENCIA (W)
HORAS
CONSUMO
COSTE
COSTE
LUMINARIA
INSTALADA
AÑO
AÑO (kWh)
kWh (€)
ANUAL (€)
INCANDESCENTE 40W
6
40
240
1.100
264,00
0,14 €
37,50 €
LED 12W
6
12
72
1.100
79,20
0,14 €
11,25 €
AHORRO
26,25 €
Ahorro en mantenimiento: COSTE CAMBIO COSTE CAMBIO MANO DE LÁMPARA/AÑO OBRA
UDS.
VIDA ÚTIL
NUMERO CAMBIOS /AÑO
COSTE TOTAL/AÑO
INCANDESCENTE 40W
6
2.000
0,55
9,90 €
16,50 €
26,40 €
LED 12W
6
25.000
0,04
6,60 €
1,32 €
7,92 €
AHORRO
18,48 €
En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de las propuestas de mejora, incluyendo gasto de energía, coste y toneladas de CO2:
SISTEMA ACTUAL
ENERGÍA (kWh)
COSTE (€)
Tm CO2
264,00
63,90 €
0,1212
SISTEMA PROPUESTO
79,20
19,17 €
0,0364
AHORRO /AÑO
184,80
44,73 €
0,08
44
Y el cuadro de amortización es el siguiente:
MEJORA 5 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
276,21 € 70,00% 184,80 70,00% 44,73 € 6,2
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
45
3.4.2 SUSTITUCIÓN DE LUMINARIAS INCANDESCENTE DE 100W POR LUMINARIAS LED DE 17W: BAÑOS Esta propuesta de mejora es para la sustitución de las 10 luminarias incandescentes de los baños del colegio. Este cambio se considera de interés debido a que supone un ahorro energético en torno al 80% del consumo, siendo muy económica en cuanto a la inversión. El cambio se justifica porque la luminosidad proporcionada por los led es del mismo orden (incluso mayor) que la luminosidad dada por las incandescentes. A partir de los datos anteriores, se estima el ahorro en consumo de energía eléctrica y en mantenimiento que se puede alcanzar mediante la instalación de estas luminarias de mayor eficacia: Ahorro en consumo de energía eléctrica: UDS.
POTENCIA (W)
POTENCIA (W)
HORAS
CONSUMO
COSTE
COSTE
LUMINARIA
INSTALADA
AÑO
AÑO (kWh)
kWh (€)
ANUAL (€)
INCANDESCENTE 100W
10
100
1.000
660
660,00
0,15 €
97,61 €
LED 17W
10
17
170
660
112,20
0,15 €
16,59 €
AHORRO
81,02 €
Ahorro en mantenimiento: COSTE CAMBIO COSTE CAMBIO MANO DE LÁMPARA/AÑO OBRA
UDS.
VIDA ÚTIL
NUMERO CAMBIOS /AÑO
COSTE TOTAL/AÑO
INCANDESCENTE 100W
10
2.000
0,33
9,90 €
16,50 €
26,40 €
LED 17W
10
25.000
0,03
13,46 €
1,32 €
14,78 €
AHORRO
11,62 €
En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de las propuestas de mejora, incluyendo gasto de energía, coste y toneladas de CO2:
ENERGÍA (kWh)
COSTE (€)
Tm CO2
SISTEMA ACTUAL
660,00
124,01 €
0,3029
SISTEMA PROPUESTO
112,20
31,38 €
0,0515
AHORRO /AÑO
547,80
92,63 €
0,25
46
Y el cuadro de amortización es el siguiente:
MEJORA 6 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
858,67 € 83,00% 547,80 74,70% 92,63 € 9,3
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
47
3.5 INSTALACIÓN DE DETECTORES DE PRESENCIA Esta medida de ahorro consiste en la instalación de detectores de presencia en los baños y zonas de paso para evitar que las luminarias permanezcan encendidas mientras no se está haciendo uso de dichos espacios.
El sistema propuesto consiste en detectores de movimiento inalámbricos compuestos por un detector de movimiento y un receptor, que deben trabajar conjuntamente. La comunicación es vía radiofrecuencia y tienen un alcance de hasta 200m (campo abierto). Esta propuesta es para la instalación de detectores de movimiento en las siguientes zonas: Edificio educación primaria: -
Pasillo planta baja
-
Hall de entrada a sala de profesores
-
Aseos de chicos planta baja
-
Aseos de chicas y pasillo de acceso a dichos aseos planta baja
-
Pasillo planta 1
-
Aseo chicas planta 1
-
Aseo minusválidos chicas
-
Aseo chicos planta 1
-
Aseo minusválidos chicos
Edificio educación infantil: -
Pasillo planta baja
-
Pasillo planta 1
-
Aseos planta 1
En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de las propuestas de mejora, incluyendo consumo de energía, coste y toneladas de CO2:
48
SISTEMA ACTUAL SISTEMA PROPUESTO AHORRO /AÑO
ENERGÍA (kWh)
COSTE (€)
Tm CO2
4.165,62
794,48
1,9120
705,06
133,59
0,3236
3.460,56
660,89 €
1,59
Y el cuadro de amortización es el siguiente:
MEJORA 7 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
6.717,10 83,07% 3.460,56 83,18% 660,89 € 10,2
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
49
3.6 INSTALACIÓN DE INTERRUPTORES CREPUSCULARES Esta medida de ahorro consiste en la instalación de un interruptor crepuscular en el vestíbulo del edificio de educación infantil. Se estima que las luminarias pasan de estar encendidas 5 horas al día a una hora al día. Los interruptores crepusculares encienden y apagan la luz en función del valor de luminosidad que se haya ajustado, es decir, si el aporte exterior de luz se encuentra por encima del nivel fijado, se apagan las luminarias, y si el aporte exterior es insuficiente, se encienden. Esto permite controlar la iluminación en instalaciones municipales de forma eficiente desde el punto de vista energético.
- Instalación en superficie o en poste. - Nivel de luminosidad regulable: 5 – 300Lux. - Sensor incorporado en la propia caja. - Retardo térmico incorporado para evitar maniobras erróneas provocadas por cambios bruscos de iluminación. - Avisador luminoso de conexión. En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de las propuestas de mejora, incluyendo consumo de energía, coste y toneladas de CO2:
ENERGÍA (kWh)
COSTE (€)
Tm CO2
SISTEMA ACTUAL
1.359,60
271,60
0,6241
SISTEMA PROPUESTO
1.087,68
217,28
0,4992
271,92
54,32 €
0,12
AHORRO /AÑO
50
Y el cuadro de amortización es el siguiente:
MEJORA 8 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
560,69 20,00% 271,92 20,00% 54,32 € 10,3
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
51
3.7 EQUIPO MONITORIZACIÓN EFERGY El contador Instantáneo de electricidad Efergy es muy útil para reducir tu consumo pues informa en tiempo real del consumo eléctrico que se produce. Con el contador Efergy podrás: •
Controlar tu consumo eléctrico.
•
Identificar los equipos que más consumen.
•
Ver y comparar tus consumos históricos diarios, semanales y mensuales.
•
Muestra los valores promedio de tu consumo diario, semanal y/o mensual.
El contador Efergy se instala colocando el toroide sobre el cable de fase del cuadro eléctrico. El transmisor emite la información al monitor portátil instantáneamente. Muestra la potencia de todo el negocio en cada instante (kW), el coste por hora (€/hora) y al mismo instante te muestra el promedio de consumo diario en kWh. Aunque el fabricante considera una reducción del consumo del 15% a causa de la información instantánea disponible mediante el sistema de monitorización, en FNeNERGIA estimamos este ahorro en un 5%.
El balance de la propuesta es el siguiente:
ENERGÍA (kWh)
COSTE (€)
Tm CO2
SISTEMA ACTUAL
80.786,00
12.648,99
37,08
SISTEMA PROPUESTO
76.746,70
12.016,54
35,23
4.039,30
632,45
1,85
AHORRO /AÑO
52
Y el cuadro de amortización es el siguiente:
MEJORA 9 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
150,00 € 5,00% 4.039,30 5,00% 632,45 € 0,2
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
53
3.8 INSTALACIÓN DE RELOJ PROGRAMABLE La siguiente propuesta de mejora es la instalación de un programador horario en cada cuadro
eléctrico
de
cada
edificio
para
desconectar
la
iluminación
del
local
automáticamente a partir de la hora programada, para evitar que puedan quedar luminarias encendidas durante las horas en las que no se está haciendo uso del local. Se estima que un 5% de las luminarias se quedan encendidas todos los días del año en el que se utiliza el local. En la siguiente tabla se muestran a modo de resumen los datos obtenidos en el estudio de la propuesta de mejora, incluyendo gasto de energía, coste y toneladas de CO2:
SISTEMA ACTUAL SISTEMA PROPUESTO AHORRO /AÑO
ENERGÍA (kWh)
COSTE (€)
Tm CO2
12.587,82
1.943,88
5,78
0,00
0,00
0,00
12.587,82
1.943,88
5,78
Y el cuadro de amortización es el siguiente:
MEJORA 10 INVERSIÓN (€) AHORRO ENERGÉTICO (%) AHORRO ENERGÉTICO (kWh) AHORRO ECONÓMICO (%) AHORRO ECONÓMICO ANUAL TOTAL (€) AMORTIZACIÓN SIMPLE* (AÑOS)
1.612,39 € 100,00% 12.587,82 100,00% 1.943,88 € 0,8
*No se tienen en cuenta posibles incrementos o reducciones del precio de la energía.
54
3.9 RESUMEN PROPUESTAS DE MEJORA A modo de resumen de las medidas preliminares propuestas, se presenta la siguiente tabla, con la inversión económica prevista para la implantación de la medida, siempre teniendo en cuenta que es una estimación basada en la experiencia de estudios previos.
INVERSIÓN TOTAL (€)
AHORRO ENERGÉTICO TOTAL % (kWh)
AHORRO ECONÓMICO
REDUCCIÓN G.E.I.
%
TOTAL (€)
(Tm CO2)
AMORTIZACIÓN (AÑOS)
MEJORA 1
CAMBIO DE COMERCIALIZADORA ELÉCTRICA
-
-
-
8,53%
1.078,70
-
INMEDIATA
MEJORA 2
COMPENSACIÓN DE ENERGÍA REACTIVA
1.986,06 €
-
-
100,00%
192,55
-
10,3
MEJORA 3
SUSTITUCIÓN DE FLUORESCENTES POR ECOTUBOS (58W)
6.297,83 €
40,43%
4.412,84
43,19%
725,35
2,03
8,7
MEJORA 4
SUSTITUCIÓN DE FLUORESCENTES POR ECOTUBOS (36W)
16.513,47 €
31,16%
6.677,67
35,79%
1.217,05
3,07
13,6
MEJORA 5
SUSTITUCIÓN DE INCANDESCENTES POR LED (40W)
276,21 €
70,00%
184,80
70,00%
44,73
0,08
6,2
MEJORA 6
SUSTITUCIÓN DE INCANDESCENTES POR LED (100W)
858,67 €
83,00%
547,80
74,70%
92,63
0,25
9,3
MEJORA 7
INSTALACIÓN DE DETECTORES DE PRESENCIA
6.717,10 €
83,07%
3.460,56
83,18%
660,89
1,59
10,2
MEJORA 8
INSTALACIÓN DE INTERRUPTOR CREPUSCULAR
560,69 €
20,00%
271,92
20,00%
54,32
0,12
10,3
MEJORA 9
EQUIPO DE MONITORIZACIÓN
150,00 €
5,00%
4.039,30
5,00%
632,45
1,85
0,2
MEJORA 10
PROGRAMACIÓN HORARIO
1.612,39 €
1.943,88
5,78
0,8
6.642,55
14,77
5,3
TOTAL
34.972,42 €
100,00% 12.587,82 100,00% 39,84%
32.182,71
52,51%
55
En la siguiente tabla se resumen las reducciones de consumo, coste y emisiones de CO2 si se aplican todas las propuestas de mejora:
SITUACIÓN ACTUAL
ALCANZABLE
AHORRO (%)
CONSUMO ENERGÉTICO (kWh)
80.786,00
48.603,29
39,84%
COSTE ANUAL (€)
12.648,99
6.006,44
52,51%
EMISIONES (TmCO2)
37,08
22,31
39,83%